Standing Seam – 1 ½” Snap Lock Panel

  • Architectural Standing Seam Metal Roofing System
  • Ideal for residential and light commercial applications
  • The specially designed clip allows thermal movement
  • Tested panel for rated assemblies achieves higher performance levels

1-1/2″ Snap Lock Panel; max width 15.39″; Snap Lock Seam fastened
with (2) #10-12 x 1″ long No. 2 Phillips drive pancake head, wood
screws; One Part Clip Assembly SL150R Clip fastening metal to panel
to minimum 15/32″ plywood decking; maximum 24″ clip spacing;
Panel Rollformer: Schlebach Quadro-Plus Rollformer; Maximum
Allowable Roof Uplift Pressure (steel): -86.0 psf Main Field @
24″ Clip Spacing; Perimeter Pressure -108.5 at 12″ Clip Spacing;
Corner Pressure -116.0 psf @ 6″ Clip Spacing; Oil Canning is a
characteristic of light gauge architectural metals and is not a fl aw and therefore is not a cause for rejection.

Specifications

Design Information

    • Minimum Slope = 1-1/2″:12″
    • Actual Panel Width: 15.39″ from 20″ Coil
    • Solid Substrate Required
    • Architectural, Hydrokinetic Panel
    • Snap Seam – No Field Seaming Required
    • 24 and 26 Gauge Galvalume®
    • .032″ Aluminum
    • 16oz Copper
    • 30 Year Finish Warranty on Kynar 500 Finish
    • Weather Tight Warranty Available
    • Underlayment Required

    Test Report Summary

    • Miami Dade Building Code Compliance Approved
    • Florida Building Code 2020
    • Chapter 15: Roof Assemblies
    • Section 1504.3.2; 1505.3; 1507.4
    • Chapter 16: Structural Design
    • Chapter 22: Steel; Section 2209 Cold Form Steel
    • Chapter 23: Wood
    • Testing per TAS 125-03 Std. Requirements for
    Metal Roof Systems
    • Test Assembly #6 by Underwriters
    Laboratory for:
    a) UL 580-94, per FBC, Uplift Resistance of
    Roof Assemblies
    b) UL 1897-98, per FBC, Uplift Tests for Roof
    Covering Systems
    • Testing per TAS 100 Wind Driven Rain Test
    • FPA #9860.11 – HVHZ – 24ga
    • M-D NOA #19-0722.06 – HVHZ – 24ga